Series ZN85-40.5 Interruptor Circuitus Vacui Altae Tensionis Interioris

Descriptio Brevis:


Detalia Producti

Etiquettae Productarum

Interruptor vacuus interioris HV ZN85-40.5 est apparatus commutatorius interior triphasicus AC 50Hz 40.5kV.

♦ Modus institutionis: typus extractibilis;

♦ Mechanismus operandi: mechanismus operandi vernalis;

♦ Genus perticae: pertica composita, pertica inclusa;

♦ Usus: apparatus commutationis KYN61-40.5.

♦ Obturaculum secundarium: 58 paxilli, 64 paxilli.

Conditiones Ambientales

♦ Temperatura ambientis: -15°C ~ +40°C;

♦ Altitudo:

♦ Humiditas relativa: media diurna ;

♦ Intensitas terraemotus:

♦ Loca sine igne, periculo explosionis, sordibus gravibus, corrosione chemica, necnon vibratione intensa.

Parametri Technici Praecipui

Non

Res

Unitas

Valor

1

Tensio aestimata

kV

40.5

Duo

Current aestimatus

A

1250 1600, 2000, 2500

Tres

Currentis interruptionis circuitus brevis aestimata

kA

XXV, XXXI.V

quattuor

Currens dynamicus (cacumen)

LXIII, LXXX

quinque

Currens stabilitatis thermalis 4s

XXV, XXXI.V

sex

Currentis brevis circuitus nominalis (apicem)

LXIII, LXXX

VII

Numerus interruptionis currentis brevis circuitus aestimatus

Tempora

viginti

VIII

Ordo operandi aestimatus

O-0.3s-CO-180s-CO

IX

Tensio sustinenda frequentiae potentiae 1 min

kV

95

decem

Tensio sustinendi impulsum fulminis aestimata

CLXXXV

undecim

Vita mechanica

Tempora

Decem milia

Duodecim

Currentis commutationis singularis capacitoris aestimati

A

DCXXX

XIII

Currentis aestimata condensatorum dorsu-ad-dorsum

quadringenti

XIV

Tensio nominalis motoris accumulationis energiae

In

AC/DC 220/110

XV

Vis motoris accumulationis energiae

IN

≤230

XVI

Tempus accumulationis energiae

s

≤15

XVII

Tensio nominalis spirae claudentis/aperentis

In

DC 220/110

XVIII

Current nominalis spirae claudentis/aperentis

A

1.05 (110V) 0.96 (220V)

XIX

Spatium inter contactus apertos mm

20±2

viginti

Contactus iter

7.5±1.5

XXI

Asynchronismus aperiendi et claudendi trium phasium

ms

≤2

XXII

Tempus resilitionis clausurae contactus

≤3

XXIII

Resistentia circuitus principalis (bracchium contactus non includens)

mΩ

≤40

Delineatio Structurae Generalis et Magnitudo Installationis (unitas: mm)

♦ Pertica composita extrahendaDelineatio ZN85

♦ Palus inclusus typus extractus

Delineatio GVS16


  • Praecedens:
  • Deinde: