Polus ascendens PGS-630A onus confractus switch adhibetur ad fractionem aestimandam voltage 12/24/40.5kV, currentis aestimatio 630A, 50/60Hz systematis distribuendi vim claudendi, onus currente claudens et supra onus systematis potentiae, sectiones sponte vestigans separare potuit virtutis distributio, quae vitia occurrunt. Transitus compositus est cum moderatore electronico qui est cum technologia recentissima. Commutatio habet modos manuales, motores, remotos operationis. Moderatorem electronicum intra capsam ferro immaculatam institui volebat, ut variis condicionibus climatis adhiberi posset. Praeter haec, filum/wireless modem inclusum in archa dicione moderandi consequi potuit remotam vigilantiam et moderantem. Facile et opportunum est ad institutionem commutandi in patibulo, et sumptus exsecutionis minuere posse.
Environmental Conditions
♦ Aeris temperies:-40℃~+50℃;
♦ Relativum humiditas: CX%
♦ Altitude ≤3000m.
♦ Ventus pressura ≤700pa (aequivalet ut 34m venti celeritatem /s).
♦ Seismic intensio: 8 gradu.
♦ Installation site: Nulla ignis clades, explosio periculi, corrosio chemica et loca tremore crebra strenua).
♦ pollutio gradus: Ⅲ classis, Ⅳclass.
Type descriptiones
MPP types
♦ Murrinae bushing efficta cable exitum
♦ Purgamentum split bushing efficta cable exitum
♦ Integrative Flexilis bushing-wiring terminatio exitus
♦ cum fluctu arrestor
♦ Murrina bushing-wiring exitum terminalem
Technical Parameter
Type products | PGS-12 | PGS-24 | PGS-40.5 |
Basic Ratings | |||
Maxime ratio voltage | 15KV | 25.8KV | 40.5 KV |
Ratum continua current | 630A | 630A | 630A |
Rated frequency | 50/60Hz | 50/60Hz | 50/60Hz |
Brevi tempore sustinere current | 20KA/4s | 25KA/1s | 20KA/1s |
Facere et frangere Capacity | |||
Maxime activae onus current | 630A | 630A | 630A |
Numerus oneris intermissum res | 400times | 400times | 400times |
Brevis circuitus faciens current (apicem) | 50KA | 50KA | 50KA |
Numerus res faciendi | 5 times | 5 times | 5 times |
Cable incurrens current | 25A | 25A | 25A |
Recta currentes præcipiens | 1.5A | 1.5A | 2A |
Clausa loop circuit current | 630A | 630A | 630A |
Nullo onus TRANSFIGURATOR solveret current | 22A | 22A | 22A |
Potestas Frequency sustinere Current Test | |||
10s (infectum test), phase- phase-terrae, per contactos apertos | 45KV | 50KV | 70KV |
1min (teste arida), terra, Phase ad terram | 50KV | 60KV | 95KV |
1min (arida test), per aperta contactus | 50KV | 60KV | 110KV |
Impetus Current Test (1.2 x 50 μs ) | |||
Phase-ad-phase, phase-ad-terram | 85 KV | 150KV | 195KV |
Per aperta contactus | 95KV | 150KV | 215KV |
Aliae Ratings & Specifications | |||
Arcus internus test | 20kA /0.1 s | 20kA /0.1 s | 20kA /0.1 s |
Arcus exstinctionis medium | SF6Gas | SF6Gas | SF6Gas |
Insulatio medium | SF6Gas | SF6Gas | SF6Gas |
Creepage procul (murrina) | 550mm | 840mm | 1055mm |
Spatium Creepage (Pii) | 610mm | 900mm | 1250mm |
IP level | 54 | 54 | 54 |
Operatio euismod | |||
Claudendo / foramen tempore | 1sec | 1sec | 1sec |
Mechanica operationes (praestatur) | 10000times | 10000times | 10000times |
Temperatus operating (* genus manual) | -25(-40)~70℃ | -25(-40)~70℃ | -25(-40)~70℃ |
Gas Pressura | |||
Rated pressura working (kg/cm2 G, in 20°C) | 0.7 | 1.0 | 1.0 |
Explosio-praesidium apparatu actio pressura (kg/cm2 G) | 4~6 | 4~6 | 4~6 |
Minimum opus pressura (kg/cm2 G) | 0.05 | 0.0 | 0.0 |
Gas lacus rate (cc/s) | ≤1% | ≤1% | ≤1% |
Super Dimensiones
Dimensio (mm) | InstallationDimension(mm) | Sarcina mole (mm) | Reptant procul ofbusing (mm) | |||
A | B | C | Longitudo Latitudo | Longitudo×Width×high | ||
10KV | 225 | 435 | 500 | 500×390 | 1100× 900×700 | 556 |
24KV | 300 | 435 | 500 | 500×390 | 1300×1100×700 | 840 |
40.5 KV | 350 | 435 | 500 | 700×390 | 1400×1200×700 | 1250 |