PGS Series Outdoor High intentione SF6 Load Break Switch

Description:


Product Detail

Product Tags

Polus ascendens PGS-630A onus confractus switch adhibetur ad fractionem aestimandam voltage 12/24/40.5kV, currentis aestimatio 630A, 50/60Hz systematis distribuendi vim claudendi, onus currente claudens et supra onus systematis potentiae, sectiones sponte vestigans separare potuit virtutis distributio, quae vitia occurrunt. Transitus compositus est cum moderatore electronico qui est cum technologia recentissima. Commutatio habet modos manuales, motores, remotos operationis. Moderatorem electronicum intra capsam ferro immaculatam institui volebat, ut variis condicionibus climatis adhiberi posset. Praeter haec, filum/wireless modem inclusum in archa dicione moderandi consequi potuit remotam vigilantiam et moderantem. Facile et opportunum est ad institutionem commutandi in patibulo, et sumptus exsecutionis minuere posse.

Environmental Conditions

♦ Aeris temperies:-40℃~+50℃;

♦ Relativum humiditas: CX%

♦ Altitude ≤3000m.

♦ Ventus pressura ≤700pa (aequivalet ut 34m venti celeritatem /s).

♦ Seismic intensio: 8 gradu.

♦ Installation site: Nulla ignis clades, explosio periculi, corrosio chemica et loca tremore crebra strenua).

♦ pollutio gradus: Ⅲ classis, Ⅳclass.

Type descriptiones

wef *

MPP types

forum

♦ Murrinae bushing efficta cable exitum

htr (1)

♦ Purgamentum split bushing efficta cable exitum

htr (2)

♦ Integrative Flexilis bushing-wiring terminatio exitus

htr (3)

♦ cum fluctu arrestor

htr (4)
htr (5)

♦ Murrina bushing-wiring exitum terminalem

Technical Parameter

Type products PGS-12

PGS-24

PGS-40.5
Basic Ratings
Maxime ratio voltage 15KV

25.8KV

40.5 KV
Ratum continua current 630A 630A 630A
Rated frequency 50/60Hz

50/60Hz

50/60Hz
Brevi tempore sustinere current 20KA/4s

25KA/1s

20KA/1s
Facere et frangere Capacity
Maxime activae onus current 630A 630A 630A
Numerus oneris intermissum res 400times

400times

400times
Brevis circuitus faciens current (apicem) 50KA 50KA 50KA
Numerus res faciendi 5 times

5 times

5 times
Cable incurrens current 25A 25A 25A
Recta currentes præcipiens 1.5A 1.5A 2A

 

Clausa loop circuit current 630A 630A 630A
Nullo onus TRANSFIGURATOR solveret current 22A 22A 22A
Potestas Frequency sustinere Current Test
10s (infectum test), phase- phase-terrae, per contactos apertos 45KV 50KV 70KV
1min (teste arida), terra, Phase ad terram 50KV 60KV 95KV
1min (arida test), per aperta contactus 50KV 60KV 110KV
Impetus Current Test (1.2 x 50 μs )
Phase-ad-phase, phase-ad-terram 85 KV 150KV 195KV
Per aperta contactus 95KV 150KV 215KV
Aliae Ratings & Specifications
Arcus internus test 20kA /0.1 s 20kA /0.1 s 20kA /0.1 s
Arcus exstinctionis medium SF6Gas SF6Gas SF6Gas
Insulatio medium SF6Gas SF6Gas SF6Gas
Creepage procul (murrina) 550mm 840mm 1055mm
Spatium Creepage (Pii) 610mm 900mm 1250mm
IP level 54 54 54
Operatio euismod
Claudendo / foramen tempore 1sec 1sec 1sec
Mechanica operationes (praestatur) 10000times 10000times 10000times
Temperatus operating (* genus manual) -25(-40)~70℃ -25(-40)~70℃ -25(-40)~70℃
Gas Pressura
Rated pressura working (kg/cm2 G, in 20°C) 0.7 1.0 1.0
Explosio-praesidium apparatu actio pressura (kg/cm2 G) 4~6 4~6 4~6
Minimum opus pressura (kg/cm2 G) 0.05 0.0 0.0
Gas lacus rate (cc/s) ≤1% ≤1% ≤1%

Super Dimensiones

jty (1)

jty (2)

Dimensio (mm) InstallationDimension(mm) Sarcina mole (mm) Reptant procul ofbusing (mm)
A B C Longitudo Latitudo Longitudo×Width×high
10KV 225 435 500 500×390 1100× 900×700 556
24KV 300 435 500 500×390 1300×1100×700 840
40.5 KV 350 435 500 700×390 1400×1200×700 1250

  • Previous: